No. Name Setting Range DefaultT1-07 Motor Base Speed 0 to 24000 r/min 1750 r/minn T1-11: Motor Iron LossProvides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor ironloss that the drive automatically calculated when the motor capacity was entered to T1-02. Enter the motor iron loss valuelisted to T1-11 if the motor test report is available.No. Name Setting Range DefaultT1-11 Motor Iron Loss 0 to 65535 W Determined byE2-11n T1-12: T1 Tuning StartSet T1-12 to 0 to start IM Auto-Tuning.No. Name Setting Range DefaultT1-12 T1 Tuning Start 0 –u T2: Parameter Settings during PM Motor Auto-TuningThe T2-oo parameters are used to set the Auto-Tuning input data for PM motor tuning.n T2-01: PM Motor Auto-Tuning Mode SelectionNo. Name Setting Range DefaultT2-01 PM Motor Auto-Tuning Mode Selection 0 to 2; 14 0Setting 0: PM Motor Parameter SettingsSetting 1: PM Stationary Auto-TuningSetting 2: PM Stationary Auto-Tuning for Stator ResistanceSetting 14: PM Rotational Auto-Tuningn T2-02: PM Motor Code SelectionIf the drive is operating a Yaskawa PM motor from the SMRA, SSR1, or SST4 series, enter the motor code in T2-02 toautomatically set parameters T2-03 through T2-09. Use the motor nameplate or motor test report values to set parametersT2-10 to T2-14. If the drive is operating a specialized motor or a motor designed by a manufacturer other than Yaskawa, setT2-02 to FFFF and enter the data from the motor nameplate or the motor test report as prompted.Only the designated PM motor codes may be entered. The PM motor codes accepted by the drive will differ depending on theselected control mode. Refer to E5: PM Motor Settings on page 64 for motor codes.No. Name Setting Range DefaultT2-02 PM Motor Code Selection 0000 to FFFF Determined by o2-04n T2-03: PM Motor TypeSelects the type of PM motor the drive will operate.No. Name Setting Range DefaultT2-03 PM Motor Type 0, 1 1Setting 0: IPM motorSetting 1: SPM motorn T2-04: PM Motor Rated PowerSpecifies the motor rated power in kilowatts.No. Name Setting Range DefaultT2-04 PM Motor Rated Power 0.00 to 650.00 kW Determined by o2-041.12 T: Motor TuningYASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual 1611 Parameter Details