Terminal V21. View the value set to F4-02 (Terminal V2 Monitor Gain) on the digital operator. A voltage equal to 100% of theparameter being viewed in F4-03 will be output from terminal V2.2. Adjust F4-04 viewing the monitor connected to the terminal V2.3. View the value set to F4-06 on the digital operator, terminal V2 will output a voltage equal to 0% of the parameterbeing set in F4-03.4. Adjust F4-06 viewing the output signal on the terminal V2.n F4-07, F4-08: Terminal V1, V2 Signal LevelSets the output signal level for terminals V1 and V2.No. Parameter Name Setting Range DefaultF4-07 Terminal V1 Signal Level 0, 1 0F4-08 Terminal V2 Signal Level 0, 1 0Setting 0: 0 to 10 VSetting 1: -10 to 10 Vu F5: Digital Output Card SettingsThese parameters set the drive for operation with the digital output option card DO-A3. Refer to the instruction manualpackaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.n F5-01 through F5-08: Digital Output Option Card Terminal Function SelectionWhen F5-09 = 2, the parameters listed in the table below assign functions to the output terminals on the option card.No. Name Setting Range DefaultF5-01 Terminal P1-PC Output Selection 0 to 1B6 0: During runF5-02 Terminal P2-PC Output Selection 0 to 1B6 1: Zero speedF5-03 Terminal P3-PC Output Selection 0 to 1B6 2: Speed agreeF5-04 Terminal P4-PC Output Selection 0 to 1B6 4: Frequency detection 1F5-05 Terminal P5-PC Output Selection 0 to 1B6 6: Drive readyF5-06 Terminal P6-PC Output Selection 0 to 1B6 37: During frequency outputF5-07 Terminal M1-M2 Output Selection 0 to 1B6 F: Not usedF5-08 Terminal M3-M4 Output Selection 0 to 1B6 F: Not usedn F5-09: DO-A3 Output Mode SelectionDetermines how the DO-A3 option card works with the drive.No. Parameter Name Setting Range DefaultF5-09 DO-A3 Output Mode Selection 0 to 2 0Note: Refer to TOBP C730600 41 Yaskawa AC Drive-Option DO-A3 Installation Manual for more details on F5-09 settings.Setting 0: Separate Output Functions for Each of 8 TerminalsSetting 1: Binary OutputSetting 2: Output Functions Assigned by F5-01 through F5-08u F6 and F7: Communication Option CardThese parameters configure communication option cards and communication fault detection methods.n F6-01: Communications Error Operation SelectionDetermines drive operation when a communication error occurs.1.6 F: Option SettingsYASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual 691 Parameter Details