<4> Default setting is dependent on parameter A1-02, Control Mode Selection.<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.<6> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.<7> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.<8> When using PM motors, the default setting is determined by the motor code set to E5-01.<9> The drive changes these settings when Auto-Tuning is performed.u E2: Motor 1 ParametersNo.(Addr.Hex) Name LCD Display Description Values PageE2-01(030E) Motor Rated Current Motor Rated FLASets the motor nameplate full load current in amps.Automatically set during Auto-Tuning. Default: <1>Min.: 10% ofdrive ratedcurrentMax.: 150% ofdrive ratedcurrent <2>62E2-02(030F) Motor Rated Slip Motor Rated SlipSets the motor rated slip. Automatically set duringAuto-Tuning. Default: <1>Min.: 0.00 HzMax.: 20.00 Hz62E2-03(0310) Motor No-Load Current No-Load CurrentSets the no-load current for the motor. Automatically set duringAuto-Tuning. Default: <1>Min.: 0.00 AMax.: E2-01 <2>62E2-04(0311) Number of Motor Poles Number of Poles Sets the number of motor poles. Automatically set duringAuto-Tuning. Default: 4Min.: 2Max.: 48 63E2-05(0312) Motor Line-to-LineResistance Term ResistanceSets the phase-to-phase motor resistance. Automatically setduring Auto-Tuning. Default: <1>Min.: 0.000 ΩMax.: 65.000 Ω63E2-10(0317) Motor Iron Loss forTorque Compensation Motor Iron LossSets the motor iron loss. Default: <1>Min.: 0 WMax.: 65535 W63E2-11(0318) Motor Rated Power Mtr Rated PowerSets the motor rated power in kilowatts (1 HP = 0.746 kW).Automatically set during Auto-Tuning. Default: <1>Min.: 0.00 kWMax.: 650.00 kW63<1> Default setting is dependent on parameter o2-04, Drive Model Selection.<2> Display is in the following units:2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A unitsu E5: PM Motor SettingsNo.(Addr.Hex) Name LCD Display Description Values PageE5-01(0329)<1>Motor Code Selection(for PM Motors) PM Mtr Code SelOLV/PMOLV/PMEnter the Yaskawa motor code for the PM motor being used.Various motor parameters are automatically set based on thevalue of this parameter. Settings that were changed manuallywill be overwritten by the defaults of the selected motor code.Note: 1. Set to FFFF when using a non-Yaskawa PMmotor or a special motor.2. If an alarm or hunting occurs despite using amotor code, enter the value indicated on thenameplate.Default: <2>Min.: 0000Max.: FFFF <4>64E5-02(032A)<1>Motor Rated Power (forPM Motors) PM Mtr Capacity OLV/PMOLV/PMSets the rated capacity of the motor.Default: <3>Min.: 0.10 kWMax.: 650.00 kW64A.7 E: Motor Parameters208 YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual