1.7 H: Terminal FunctionsH parameters assign functions to the external terminals.u H1: Multi-Function Digital Inputsn H1-01 to H1-08: Functions for Terminals S1 to S8These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in Table1.31.No. Parameter Name SettingRange DefaultH1-01 Multi-Function Digital Input Terminal S1 Function Selection 1 to B2 40 (F) <1> : Forward Run Command (2-Wire sequence)H1-02 Multi-Function Digital Input Terminal S2 Function Selection 1 to B2 41 (F) <1> : Reverse Run Command (2-Wire sequence)H1-03 Multi-Function Digital Input Terminal S3 Function Selection 0 to B2 24: External Fault (N.O., always detected, coast to stop)H1-04 Multi-Function Digital Input Terminal S4 Function Selection 0 to B2 14: Fault ResetH1-05 Multi-Function Digital Input Terminal S5 Function Selection 0 to B2 3 (0) <1> : Multi-Step Speed Reference 1H1-06 Multi-Function Digital Input Terminal S6 Function Selection 0 to B2 4 (3) <1> : Multi-Step Speed Reference 2H1-07 Multi-Function Digital Input Terminal S7 Function Selection 0 to B2 6 (4) <1> : Jog Reference SelectionH1-08 Multi-Function Digital Input Terminal S8 Function Selection 0 to B2 8: External Baseblock Command<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).Table 1.31 Multi-Function Digital Input Terminal SettingsSetting Function Page0 3-Wire Sequence 793 Multi-Step Speed Reference 1 794 Multi-Step Speed Reference 26 Jog reference Selection 797 Accel/Decel Time Selection 1 798 Baseblock Command (N.O.) 809 Baseblock Command (N.C.)A Accel/Decel Ramp Hold 80B Drive Overheat Alarm (oH2) 80C Analog Terminal Input Selection 80F Through Mode 8010 Up Command 8011 Down Command12 Forward Jog 8113 Reverse Jog14 Fault Reset 8215 Fast Stop (N.O.) 8217 Fast Stop (N.C.) 8218 Timer Function Input 8219 PID Disable 821B Program Lockout 821E Reference Sample Hold 8320 to 2F External Fault 8330 PID Integral Reset 8431 PID Integral Hold 8434 PID Soft Starter Cancel 8435 PID Input Level Selection 8440 Forward Run Command (2-Wire sequence) 8441 Reverse Run Command (2-Wire sequence)Setting Function Page42 Run Command (2-Wire sequence 2) 8443 FWD/REV Command (2-Wire sequence 2)44 Offset Frequency 18545 Offset Frequency 246 Offset Frequency 347 Node Setup 8550 Motor Pre-Heat 2 8551 Sequence Timer Disable 8552 Sequence Timer Cancel 8560 Motor Pre-Heat 1 8561 External Speed Search Command 1 8562 External Speed Search Command 2 8563 Field Weakening 8567 Communications Test Mode 8569 Jog 2 856A Drive Enabled 866D AUTO Mode Select 866E HAND Mode Select 8670 Drive Enable2 86A4 BP Emergency Override 86A5 BP Drive/Bypass Selection 86A6 BP BAS Interlock 86A7 BP Customer Safeties 86A8 PI2 Disable (N.O.) 86A9 PI2 Disable (N.C.) 87AA PI2 Inverse Operation 87AB PI2 Integral Reset 87AC PI2 Integral Hold 87AD Select PI2 Parameters 871.7 H: Terminal Functions78 YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual