Set the Line-to-Line ResistanceE2-05 is normally set during Auto-Tuning. If Auto-Tuning cannot be performed, contact the motor manufacturer to determinethe correct resistance between motor lines. The motor test report can also be used to calculate this value using the formulasbelow:• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C (167 °F).• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C (167 °F).• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C (239 °F).Set the Motor Iron Loss for Torque CompensationOnly required when using V/f Control. Enter this value in watts to E2-10. The drive uses this setting to improve the precisionof torque compensation.u E5: PM Motor SettingsThese parameters set the motor data of a PM motor.Perform Auto-Tuning for PM motors. The motor data can be entered manually, if known.Note: 1. E5-oo parameters are visible only when a OLV/PM motor control mode is selected (A1-02 = 5).2. E5-oo parameters are not reset when the drive is initialized using parameter A1-03.n E5-01: Motor Code Selection (for PM Motors)When using Yaskawa motors, set the motor code for the PM motor being used. The drive automatically sets several parametersto appropriate values depending on the motor code.Setting parameter E5-01 to FFFF allows the motor data to be manually set using the E5-oo parameters.No. Parameter Name Setting Range DefaultE5-01 Motor Code Selection (for PM Motors) 0000 to FFFF Determined byA1-02 and o2-04Note: 1. E5-oo parameters are not reset when the drive is initialized using parameter A1-03.2. When E5-01 is set to a value other than FFFF, the drive will not initialize using parameter A1-033. Changing E5-01 to FFFF from value other than FFFF will not change the values of parameters E5-02 through E5-24.4. Set E5-01 to FFFF when using a motor other than a Yaskawa SMRA, SSR1, or SST4 series.5. Default settings is Yaskawa SSR1 Series (1750 r/min)6. Selection may vary depending on the motor code entered to E5-01.7. If an alarm or hunting occurs despite using a motor code, enter the value indicated on the nameplate.Figure 1.30 explains the motor code setting.0: 1800 r/min Series1: 3600 r/min Series2: 1750 r/min Series3: 1450 r/min Series4: 1150 r/min SeriesF: Special MotorMotor Voltage Classand Capacity0: Pico Motor(SMRA Series)1: Derated Torque for IPMMotors(SSR 1 Series)2: Rated Torque for IPMMotors(SST4 Series)Figure 1.30 PM Motor Coden E5-02: Motor Rated Power (for PM Motors)Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors.No. Parameter Name Setting Range DefaultE5-02 Motor Rated Power (for PM Motors) 0.10 to 650.00 kW Determined byE5-01n E5-03: Motor Rated Current (for PM Motors)Sets the motor rated current in amps. Automatically set when the value is entered to T2-06 during Auto-Tuning.1.5 E: Motor Parameters64 YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual