No. Name Setting Range Defaulto1-16 F1 Key Function Selection 0 to 4 0o1-17 F2 Key Function Selection 0Setting 0: StandardSetting 1: MonitorSetting 2: Drive/Bypass (DRV/BYP)Setting 3: Bypass Run (RUN BYP)Setting 4: Toggle Relay Output (RLY)n o1-18, o1-19: User-Defined Parameter Upper/LowerAllows the user to set values that can be used as reference information.No. Name Setting Range Defaulto1-18 User-Defined Parameter Upper 0 to 999 0o1-19 User-Defined Parameter Loweru o2: HOA Keypad FunctionsThese parameters determine the functions assigned to the operator keys.n o2-02: OFF Key Function SelectionDetermines if the OFF key on the HOA keypad will stop drive operation when the drive is controlled from a remote source(i.e., not from HOA keypad).Note: The keypad OFF key is not functional when the drive is in Emergency Override.No. Name Setting Range Defaulto2-02 OFF Key Function Selection 0, 1 1Setting 0: DisabledSetting 1: EnabledThe OFF key will terminate drive operation even if the Run command source is not assigned to the HOA keypad. Cycle theRun command to restart the drive if the drive has been stopped by pressing the OFF key.n o2-03: User Parameter Default ValueAfter completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the values,parameter A1-03 (Initialize Parameters) will offer the choice of "1110: User Initialize". Selecting 1110 resets all parametersto the user-set default values. Refer to A1-03: Initialize Parameters on page 11 for details on drive initialization.No. Name Setting Range Defaulto2-03 User Parameter Default Value 0 to 2 0Setting 0: No Change (Awaiting Command)Setting 1: Set User Initialize ValuesThe current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing theENTER key saves the values and returns the display to 0.Setting 2: Clear User Initialize ValuesAll user-set defaults for “User Initialize” are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values andreturns the display to 0.n o2-04: Drive Model SelectionSet this parameter when replacing the control board or the terminal board. Refer to Defaults by Drive Model on page 259 forinformation on drive model selection.NOTICE: Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.1.10 o: Operator-Related Settings136 YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual