No. Name Setting Range DefaultS4-02 BP Energy Save Bypass Trigger Level 0 to 20 Hz 0 Hzn S4-03: BP Energy Save Bypass TimerSets the time in seconds that the drive should run at the specified speed before entering Energy Save Bypass mode.No. Name Setting Range DefaultS4-03 BP Energy Save Bypass Timer 10 to 60000 s 60 sn S4-04: BP Energy Save Bypass Speed IncreaseSets the value in Hz that the drive will increase the output frequency above E1-04 before performing an Energy Save transferto bypass.No. Name Setting Range DefaultS4-04 BP Energy Save Bypass Speed Increase 0 to 10 Hz 6 Hzu S5: HOA Keypad Parametersn S5-01: HAND Frequency Reference SelectionSelects the speed command input source in HAND mode.No. Name Setting Range DefaultS5-01 HAND Frequency Reference Selection 0 to 4 0Setting 0: HOA KeypadSetting 1: TerminalsSetting 2: d1-16Setting 3: S5-05Setting 4: Determined by b1-01n S5-02: HAND/AUTO During Run SelectionSelects if drive will permit switching between HAND and AUTO modes while running.No. Name Setting Range DefaultS5-02 HAND/AUTO During Run Selection 0 or 1 1Setting 0: DisabledSetting 1: Enabledn S5-03: HAND Mode PID SelectionSelects whether PID control is enabled or disabled when in HAND mode.No. Name Setting Range DefaultS5-03 HAND Mode PID Selection 0 or 1 1Setting 0: DisabledSetting 1: Enabledn S5-04: HAND Mode Behavior SelectionSelects the behavior of HAND mode.No. Name Setting Range DefaultS5-04 HAND Mode Behavior Selection 0 to 2 11.11 S: Special Parameters156 YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual