n o3-01: Copy Function SelectionInstructs the drive to Read, Write, or Verify parameter settings.No. Name Setting Range Defaulto3-01 Copy Function Selection 0 to 3 0Setting 0: Copy Select (No Function)Setting 1: INV --> OP READCopies all parameters from the drive to the HOA keypad.Note: The copy protection for the HOA keypad is enabled by default. Set o3-01 to 1 to unlock copy protection.Setting 2: OP --> INV WRITECopies all parameters from the HOA keypad to the drive.Setting 3: OP<-->INV VERIFYCompares the parameters in the drive with the parameter settings saved on the HOA keypad for matches.n o3-02: Copy Allowed SelectionAllows and restricts the use of the Copy function.No. Name Setting Range Defaulto3-02 Copy Allowed Selection 0, 1 0Setting 0: DisabledSetting 1: Enabledu o4: Maintenance Monitor Settingsn o4-01: Cumulative Operation Time SettingSets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track ofoperation time from some desired value. Total operation time can be viewed in monitor U4-01.Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will alsobe displayed in monitor U4-01.No. Name Setting Range Defaulto4-01 Cumulative Operation Time Setting 0 to 9999 h 0 hn o4-02: Cumulative Operation Time SelectionSelects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in monitor U4-01.No. Name Setting Range Defaulto4-02 Cumulative Operation Time Selection 0, 1 1Setting 0: Power on TimeThe drive logs the time it is connected to a power supply, regardless of whether the motor is running.Setting 1: Run TimeThe drive logs the time that the output is active including when the Run command is active (even if the motor is not rotating)and when there is voltage output.n o4-03: Cooling Fan Operation Time SettingSets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 afterreplacing the cooling fan.Note: 1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. “300”will be displayed in monitor U4-03.2. The cooling fan may require maintenance at an earlier date in harsher environments.No. Name Setting Range Defaulto4-03 Cooling Fan Operation Time Setting 0 to 9999 h 0 h1.10 o: Operator-Related Settings138 YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual