Section 11 – History Log11-3Mounting and Wiring the Printer Interface UnitThe printer interface unit must be installed in a separately ordered PID box. It is powered locally by aseparately ordered plug-in transformer rather than by the RS-485 bus.Step Action1 Mount the printer interface unit in the separately ordered PID box.2 Connect the printer to the interface unit using the 18’ cable supplied.3 Connect the AC wires from the 12VAC transformer. You may plug the transformer intothe 120VAC outlet, but do not plug in the transformer for the printer at this time. Plugthat transformer in when the installation of the system is complete.Addressing the Printer Interface UnitThe printer interface unit(s) use communication group number 02 on the RS-485 bus, and unitnumbers 0 (master printer) and 7 (slave printers). The printer interface unit comes pre-addressed forcommunication group number 2 and unit number 0, so no adjustment to the addressing is required ifonly one printer interface is being used.If additional printer interfaces are being used, set jumpers E2 through E4 for unit number 7. SeeFigure 11-1.Displaying and Printing the History LogThe FOCUS 200 PLUS system can display the history log on the screen of an operating panel orproduce a hard-copy printout of events. The operating panel will display the last event that occurred,and, by means of selector buttons, you can scroll through the history log.The printer can be operated on-line or off-line. When the printer is operated on-line, events will beprinted out as they occur. When operated off-line, printouts are made on command from an operatingpanel. A printout can be made of the most recent 60 events or the most recent 500 events, and willbegin with the oldest event. The printout can be terminated at any time by selecting Stop Print.To display or print the history log, proceed through the following prompts:< ? Enter choice:< Lesson Turn on >< See alarms Reset >< Quit More >Enter the Service Code. Action Menu #1 is displayed.Select More twice.< ? Enter choice:< Bypass History >< Status Time >< Previous More >Action Menu #3 is displayed.Select History to display the next screen.< ? See history:On this screen >On Printer >< QuitThis is the See History Screen.Select On this screen to display the history on the operatingpanel’s screen.Select On Printer to print the history.Select Quit to move back to Action Menu #3.09/28/98 11:06 AMPNT245 OUTPUT RST< Previous Pgdn >< Quit Next >If On this screen was selected, this screen is displayed.The first line shows the date and time of the event. The secondline shows a description of the event.Select Previous to display the previous event.Select Next to display the next event.Select Pgdn to display more detail of this event.Select Quit to move back to the See History Screen.