[180] Clock Fault The clock function has been reset todefault (2000-01-01) because of a powerfailure.[181] PreventiveMaintenance1 or more of the preventive maintenanceevents programmed inparameter 23-10 Maintenance Item haspassed the time for the specified action inparameter 23-11 Maintenance Action.[193] Sleep Mode The frequency converter/system hasturned into sleep mode. See parametergroup 22-4* Sleep Mode.[194] Broken Belt A broken belt condition has beendetected. This function must be enabledin parameter 22-60 Broken Belt Function.[196] Fire Mode The frequency converter is operating inFire mode. See parameter group 24-0* FireMode.[198] Drive Bypass To be used as signal for activating anexternal electromechanical bypass,switching the motor direct on line. See24-1* Drive Bypass.CAUTIONIf enabling the drive bypassfunction, the frequency converter isno longer safety certified (for usingthe Safe Torque Off in versionswhere included).The below setting options are all related to the cascadecontroller.Wiring diagrams and settings for parameter, see parametergroup 25-** Cascade Pack Controller for more details.[200] FullCapacityAll pumps running and at full speed.[201] Pump1RunningOne or more of the pumps controlled by thecascade controller are running. The functionalso depends on parameter 25-06 Number ofPumps. If set to [0] No, Pump 1 refers to thepump controlled by relay RELAY1 etc. If set to[1] Yes, Pump 1 refers to the pump controlledby the frequency converter only (without anyof the built-in relays involved), and Pump 2 tothe pump controlled by the relay RELAY1. SeeTable 3.15.[202] Pump2RunningSee [201] Pump1 Running[203] Pump3RunningSee [201] Pump1 RunningSetting inparameter group5-3* Digital OutputsSetting in parameter 25-06 Number ofPumps[0] No [1] Yes[200] Pump 1RunningControlled byRELAY1Frequency convertercontrolled[201] Pump 2RunningControlled byRELAY2Controlled byRELAY1[203] Pump 3RunningControlled byRELAY3Controlled byRELAY2Table 3.15 Settings5-30 Terminal 27 Digital OutputThis parameter has the options described in chapter 3.7.10 5-3*Digital Outputs. This parameter is active when VLT ® GeneralPurpose I/O MCB 101 is mounted in the frequency converter.Option: Function:[0] * No operation5-31 Terminal 29 Digital OutputThis parameter has the options described in chapter 3.7.10 5-3*Digital Outputs. The default option is listed.Option: Function:[0] * No operation5-32 Term X30/6 Digi Out (MCB 101)This parameter has the options described in chapter 3.7.10 5-3*Digital Outputs. This parameter is active when VLT® GeneralPurpose I/O MCB 101 is mounted in the frequency converter.Option: Function:[0] * No operation5-33 Term X30/7 Digi Out (MCB 101)Option: Function:[0] * No operation This parameter has the same options definedin parameter group 5-3* Digital Inputs. Thisparameter is active when VLT® GeneralPurpose I/O MCB 101 is mounted in thefrequency converter.3.7.11 5-4* RelaysParameters for configuring the timing and the outputfunctions for the relays.5-40 Function RelayArray [8](Relay 1 [0], Relay 2 [1]Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).Select options to define the function of the relays.The selection of each mechanical relay is realized in an arrayparameter.Option: Function:[0] No operationParameter Descriptions VLT® HVAC Drive FC 10298 Danfoss A/S © 10/2019 All rights reserved. M001000133