18-38 Temp. Input X48/7Range: Function:0* [-500 - 500 ] View the actual temperaturemeasured at input X48/7. Thetemperature unit is based on theselection in parameter 35-02 Term.X48/7 Temperature Unit.18-39 Temp. Input X48/10Range: Function:0* [-500 - 500 ] View the actual temperaturemeasured at input X48/10. Thetemperature unit is based on theselection in parameter 35-04 Term.X48/10 Temperature Unit.3.17.4 18-4* PGIO Data ReadoutsParameters for configuring the readout of VLT®Programmable I/O .18-43 Analog Out X49/7Range: Function:0* [0 - 30 ] Shows the actual value at output ofterminal X49/7 in V or mA. Thevalue reflects the selection inparameter 36-40 Terminal X49/7Analogue Output.18-44 Analog Out X49/9Range: Function:0* [0 - 30 ] Shows the actual value at output ofterminal X49/9 in V or mA. Thevalue reflects the selection inparameter 36-50 Terminal X49/9Analogue Output.18-45 Analog Out X49/11Range: Function:0* [0 - 30 ] Shows the actual value at output ofterminal X49/11 in V or mA. Thevalue reflects the selection inparameter 36-60 Terminal X49/11Analogue Output.3.17.5 18-5* Ref. & Feedb.NOTICESensorless readout requires set-up by MCT 10 Set-upSoftware with sensorless specific plug-in.18-50 Sensorless Readout [unit]Range: Function:0 Sensor-lessUnit*[-999999.999- 999999.999Sensor-lessUnit]18-57 Air Pressure to Flow Air FlowShows the air flow calculated using the measured pressuredifference.Range: Function:0 AirPres-ToFlowUnit*[0 - 999999AirPresTo-FlowUnit]Readout value for air pressure to airflow calculation.18-60 Digital Input 2Range: Function:0* [0 - 65535 ] Shows the signal states from theactive digital inputs.• 0 = No signal• 1 = Connected signal.Parameter Descriptions Programming GuideM0010001 Danfoss A/S © 10/2019 All rights reserved. 1733 3