15-10 Logging SourceArray [4]Option: Function:[1860] Digital Input 2[3110] Bypass StatusWord15-11 Logging IntervalArray [4]Range: Function:Sizerelated*[ 0.000 -0.000 ]Enter the interval in ms betweeneach sampling of the variables tobe logged.15-12 Trigger EventOption: Function:Selects the trigger event. When thetrigger event occurs, a window isapplied to freeze the log. The logthen retains a specified percentageof samples before the occurrence ofthe trigger event(parameter 15-14 Samples BeforeTrigger).[0] * False[1] True[2] Running[3] In range[4] On reference[5] Torque limit[6] Current Limit[7] Out of currentrange[8] Below I low[9] Above I high[10] Out of speedrange[11] Below speedlow[12] Above speedhigh[13] Out of feedb.range[14] Below feedb.low[15] Above feedb.high[16] Thermalwarning[17] Mains out ofrange[18] Reversing[19] Warning[20] Alarm (trip)15-12 Trigger EventOption: Function:[21] Alarm (triplock)[22] Comparator 0[23] Comparator 1[24] Comparator 2[25] Comparator 3[26] Logic rule 0[27] Logic rule 1[28] Logic rule 2[29] Logic rule 3[33] Digital inputDI18[34] Digital inputDI19[35] Digital inputDI27[36] Digital inputDI29[37] Digital inputDI32[38] Digital inputDI33[50] Comparator 4[51] Comparator 5[60] Logic rule 4[61] Logic rule 515-13 Logging ModeOption: Function:[0] * Log always Select [0] Log always for continuouslogging.[1] Log once ontriggerSelect [1] Log once on trigger tostart and stop logging conditionallyusing parameter 15-12 Trigger Eventand parameter 15-14 Samples BeforeTrigger.15-14 Samples Before TriggerRange: Function:50* [0 - 100 ] Enter the percentage of all samplesto be retained in the log before atrigger event occurs. See alsoparameter 15-12 Trigger Event andparameter 15-13 Logging Mode.3.15.3 15-2* Historic LogView up to 50 logged data items via the array parametersin this parameter group. Data is logged every time anevent occurs (not to be confused with SLC events). Eventsin this context are defined as a change in 1 of thefollowing areas:Parameter Descriptions Programming GuideM0010001 Danfoss A/S © 10/2019 All rights reserved. 1593 3