4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10 99Table 10. Environmental and Safety (Continued)Surge Suppression EN 61000-4-5Safety Conformance CSA C22.2, No. 107.3; UL1778 5th EditionAgency Markings NOM, UL, CUL, FCCEMC (Class A) EN 62040-2, FCC Part 15, EN 61000-4-2 level 3 Criteria B, EN61000-4-3 level 3 Criteria A, EN61000-4-4, 61000-4-5, 61000-4-6, 61000-4-81100..55 BBaatttteerryy RRaattiinnggssTable 11. Battery RatingsConfiguration (2) 60V, 9 Ah battery modules per two-battery slotVoltage 120 VdcType Sealed, maintenance–free, valve–regulated, lead–acidCharging ABM recommends 48 hours of charging after a discharge.Optional super chargers at higher current ratings are available.1100..66 OOuuttppuutt RRuunn TTiimmeessModel Nominal OutputVoltage (VAC) L-N/L-LOutput VA/WRating @ NominalInput Connection Output (See OutputReceptacles Figure74)Minimum Run timeat full powerload**Split-Phase20kVA 12-Slot110/220120/208120/24018000/1620020000/1800020000/1800020000/18000Hardwired Hardwired +OptionalReceptacles5.8 minSplit-Phase16kVA 8-Slot110/220120/208120/24016000/14400 Hardwired Hardwired +OptionalReceptacles5.8 min1100..77 WWeeiigghhttss aanndd DDiimmeennssiioonnssTable 12. Weights and DimensionsCabinet Size PackageHeightPackageLengthPackageWidthPackageWeightProductHeightProductLengthProductWidthProductWeightWith CasterTray (lbs)12 Slot UPS 118.1 cm(46.5")88.9 cm(35")64.1 cm(25.25")110.7 kg(244 lb)92.7 cm(36.5")87.6 cm(34.5")44.5 cm(17.5")77.1 kg(170 lb)93.4 kg (206lb)8 Slot UPS 88.9 cm(35")88.9 cm(35")64.1 cm(25.5")90.3 kg(199 lb)63.5 cm(25")87.6 cm(34.5")44.5 cm(17.5")56.7 kg(125 lb)73 kg(161 lb)12 Slot EBM 118.1 cm(46.5")88.9 cm(35")64.1 cm(25.5")108.5 kg(239 lb)92.7 cm(36.5")87.6 cm(34.5")44.5 cm(17.5")74.8 kg(165 lb)91.2 kg (201lb)Battery Ratings