80 4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10BBaatttteerryy SSeettttiinnggssThe Battery Settings Menu provides control of battery tests, warnings and modes.Figure 66. Battery Settings MenuLocal SettingsIn/Out settingsOn/Off settingsBattery settingsInput signalsComm settingsUser password enableUser password settingsSettingsABM On OffAuto battery testLow battery warningRestart batt. LevelLow BTR warningExternal batteryDeep disch.protect.Battery settingsABM On OffAuto battery testLow battery warningEnabled √DisabledRestart batt.level20Battery settingsLow BTR warning%Enabled √Disabled%00sec180Deep. Disch.Protect.Yes √Warranty void if noNoAuto battery testLow battery warningRestart batt. levelLow BTR warningExternal batteryAuto DetectionAuto DetectionManual EBM set.Manual batt. set.External batteryAuto DetectionAuto DetectionManual batt. set.External batteryAuto DetectionAuto DetectionManual EBM set.External batteryAuto Detection1 BMExternal batteryManual EBM set.0 StringsExternal batteryManual batt. set.0 AHAdvanced Battery Mode[Enabled] [Disabled]In ABM cycling mode:[No test] [Every ABM cycle]In constant charge mode:[No test] [Every day][Every week][Every month]Default Value: [Every ABM cycle]/[Everyweek][Capacity] [0%] … [100%][Runtime] [0min] … [60min]The alarm triggers when theset percentage of battery capacityor remaining back-up time is reached.Default Value: [20%] [3min][0%]...[100%]If set, automatic restart willoccur only when percentageof battery charge is reached.Default Value: [0%]Low Battery Warning:Below 3 min. or less thansetting capacity thershold.Default Value: [0%][Auto detection][Manual EBM set.][Manual battery set.]Default Value: [Auto detection]Using standard EBM, UPS detectsautomatically the numberof EBM connected[Yes] [No]If set to Yes, the UPS automaticallyprevents battery from deepdischarge by adapting end ofback-up time voltage threshold.Warranty void if set to No.Default Value: [Yes]Select Battery Testsand WarningsSelect Battery SettingsExternal BatteryManual EBM set.Manual batt. set.Display Menu Screens