4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10 39NOTE UPS output circuits must be installed in separate conduit systems and not shared withother electrical circuits.Figure 35. UPS Input and Output Terminal Connections+Hj*jD+L58g[nput8onnections58g8onnectionsj+H*jD+L+L58gQerminal7locks+ugg"crewsQerminalg7lock*round+ug3. Make the UPS input and output connections to the terminal blocks on the rear panel (see Figure 35 ):NOTE UPS output circuits must be installed in separate conduit systems and not shared withother electrical circuits.a. Insert the L1, N and L2 cable ends into the applicable terminal slots on the terminal block.b. Insert the G (GND) cable end into the ground lug on the rear panel.c. Secure the cables by screwing down the lug screws.4. Route and connect the AC input cables to the building service panel and the AC output cables to the loaddistribution panel as shown in Figure 36 .5. Torque the screws holding all input and output power conductors to the values specified in Table 6 .6. Install the supplied wiring connectors to the UPS input control signal wires and connect to the terminals asshown in . See , “ Figure 74 ” from signal terminal identification.UPS Electrical Installation