5-66 B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5Figure 5-24: Options for buffered report messagesBuffered Report1 BufTmRange: 0 to 4294967295 in steps of 1Default: 0 msThe entered value sets the time interval in milliseconds for the buffering of events for inclusion in a single report.Buffered Report1 TrgOpsRange: The check box for an individual bit can be enabled or notDefault: All bits enabled / trueThe TrgOps setting is bitstring that controls which trigger conditions are monitored in this report. The options are asfollows. Uncheck any trigger conditions that are not needed.– data-change– quality-change– integrity– general interrogationBuffered Report1 IntgPdRange: 0 to 4294967295 in steps of 1Default: 0 msThe entered value sets the period in milliseconds for generating Buffered Report1 integrity reports. An integrity reportincludes the values of all members of the referenced data set, whether a change has occurred or not.Each unbuffered report has the following settings.Unbuffered Report1 RptIDRange: 0 to 129 VisibleString charactersDefault: empty stringThe name of the report. The entered value sets the RptID value in Unbuffered Report1 messages, and it can be used bythe client to discriminate Unbuffered Report1 messages from other messages. If the number of characters entered iszero, the value used for RptID in messages is an ObjectReference to the report's control block, that is, "/LLN0$RP$"URCB01".Unbuffered Report1 NameRange: 0 up to 32 VisibleString charactersDefault: URCB01The entered value sets the report control block name value for Unbuffered Report1.Unbuffered Report1 DatSetRange: None, TT6DataSet1, TT6 DataSet2, …, TT3DataSet01, TT3DataSet02, …Default: NoneThis setting selects the data set whose members' status is reported in Unbuffered Report1 messages using the UR Setupsoftware designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, asdescribed later.