5-164 B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 5: SETTINGS5Figure 5-87: Trip bus logic5.7.3 Setting groupsSETTINGS CONTROL ELEMENTS SETTING GROUPSThe setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPEDELEMENTS settings menu. The active setting group can be indicated on the front display of the UR by configuring User-Programmable LEDs to display the state of the SETTING GROUP ACT FlexLogic operands.SETTING GROUPS FUNCTION — When Enabled, allows setting groups other than group 1 (the default active group) to beactivated. The default setting group is forced active while the SETTING GROUPS FUNCTION setting is Disabled.SETTING GROUPS BLK — Prevents the active setting group from changing when the selected FlexLogic operand is "On." Thiscan be useful in applications where it is undesirable to change the settings under certain conditions, such as during acontrol sequence. SETTING GROUPS SETTING GROUPSFUNCTION: EnabledRange: Disabled, Enabled SETTING GROUPS BLK:OffRange: FlexLogic operand GROUP 2 ACTIVATE ON:OffRange: FlexLogic operand GROUP 6 ACTIVATE ON:OffRange: FlexLogic operand GROUP 1 NAME: Range: up to 16 alphanumeric characters GROUP 6 NAME: Range: up to 16 alphanumeric characters SETTING GROUPEVENTS: DisabledRange: Disabled, Enabled