1-8 F60 Feeder Protection System GE Multilin1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED1 c) CONFIGURING ETHERNET COMMUNICATIONSBefore starting, verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay. Tosetup the relay for Ethernet communications, you define a Site, then add the relay as a Device at that site.The computerand UR device must be on the same subnet.12. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.13. Click the Device Setup button to open the Device Setup window, then click the Add Site button to define a new site.14. Enter the desired site name in the “Site Name” field. If desired, a short description of site can also be entered alongwith the display order of devices defined for the site. In this example, we use “Location 2” as the site name. Click theOK button when complete.15. The new site appears in the upper-left list in the EnerVista UR Setup window. Click the Device Setup button thenselect the new site to re-open the Device Setup window.16. Click the Add Device button to define the new device.17. Enter the desired name in the “Device Name” field and a description (optional) of the site.18. Select “Ethernet” from the Interface drop-down list. This displays a number of interface parameters that must beentered for proper Ethernet functionality.Figure 1–7: CONFIGURING ETHERNET COMMUNICATIONS19. Enter the relay IP address specified in the front panel SETTINGS PRODUCT SETUP COMMUNICATIONS NET-WORK IP ADDRESS in the “IP Address” field.20. Enter the relay slave address and Modbus port address values from the respective settings in the front panel SETTINGS PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL menu.21. Click the Read Order Code button to connect to the F60 device and upload the order code. If an communications erroroccurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay settingvalues.22. Click OK when the relay order code has been received. The new device is added to the Site List window (or Onlinewindow) located in the top left corner of the main EnerVista UR Setup window.The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the F60 section tobegin communications.