B-84 F60 Feeder Protection System GE MultilinB.4 MEMORY MAPPING APPENDIX BBF134ENUMERATION: PASS/FAIL0 = Fail, 1 = OK, 2 = n/aF137ENUMERATION: USER-PROGRAMMABLE PUSHBUTTONFUNCTION0 = Disabled, 1 = Self-Reset, 2 = LatchedF139ENUMERATION: DEMAND CALCULATIONS0 = Thermal Exponential, 1 = Block Interval, 2 = Rolling DemandF141ENUMERATION: SELF TEST ERRORSF143UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number)A bit value of 0 = no error, 1 = errorF144ENUMERATION: FORCED CONTACT INPUT STATE0 = Disabled, 1 = Open, 2 = ClosedBitmask Error0 Any Self Tests1 IRIG-B Failure2 Port 1 Offline3 Port 2 Offline4 Port 3 Offline5 Port 4 Offline6 Port 5 Offline7 Port 6 Offline8 RRTD Communications Failure9 Voltage Monitor10 FlexLogic Error Token11 Equipment Mismatch12 Process Bus Failure13 Unit Not Programmed14 System Exception15 Latching Output Discrepancy17 Maintenance Alert 0118 SNTP Failure19 Maintenance Alert20 Maintenance Alert21 Maintenance Alert22 Temperature Monitor23 Process Bus Trouble24 Brick Trouble25 Field RTD Trouble26 Field TDR Trouble27 Remote Device Offline28 Direct Device Offline29 Maintenance Alert30 Any Minor Error31 Any Major Error33 Maintenance Alert64 Maintenance Alert65 IEC 61850 Data Set66 Aggregator Error67 Unit Not Calibrated68 Settings Save Error69 SRAM Data Error70 Program Memory71 Watchdog Error72 Low On Memory73 Prototype Firmware74 Module Failure 0175 Module Failure 0276 Module Failure 0377 Module Failure 0478 Module Failure 0579 Module Failure 0680 Module Failure 0781 Module Failure 0882 Module Failure 0983 Incompatible H/W84 Module Failure 1085 Module Failure 1186 Module Failure 1287 High ENET Traffic89 Relay Restart90 FGM Failure91 FGM Failure92 FGM Failure93 FGM Failure94 FGM Failure95 FGM Error96 Maintenance Alert97 PHY Monitor98 Storage Media Alarm99 Wrong Transceiver100 Power Supply WarningBitmask Error