5-86 L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5File transfer by IEC 61850The L60 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as anexample.1. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.2. Select the Remote AR Name from the drop-down list. Available files appear in the File Specification area on the rightside of the window.3. With the Copy option active, select a file to transfer and click the Go button. The file is copied and displays in the Locallist on the left side of the window.4. Repeat the process to transfer any other files.Figure 5-39: File transfer by IEC 618505.3.4.13 Web server HTTP protocolSETTINGS PRODUCT SETUP COMMUNICATIONS WEB SERVER HTTP PROTOCOLThe L60 contains an embedded web server and can display pages in a web browser. The web pages are organized as aseries of menus that can be accessed starting at the L60 “Main Menu.” Web pages are read-only and are available showingDNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the L60 and acomputer to an Ethernet network, then enter the IP address of the L60 Ethernet port in a web browser.To close the port, set the port number to 0. The change takes effect when the L60 is restarted. WEB SERVER HTTP PROTOCOL HTTP TCP PORTNUMBER(80): 80Range: 0 to 65535 in steps of 1