CHAPTER 5: SETTINGS GROUPED ELEMENTSL60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL 5-2115Figure 5-114: Ground directional supervision logic5.6.6 Power swing detect (ANSI 68)SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) POWER SWING DETECT POWER SWING DETECT POWER SWINGFUNCTION: DisabledRange: Disabled, Enabled POWER SWINGSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4 POWER SWINGSHAPE: Mho ShapeRange: Mho Shape, Quad Shape POWER SWINGMODE: Two StepRange: Two Step, Three Step POWER SWINGSUPV: 0.600 puRange: 0.050 to 30.000 pu in steps of 0.001 POWER SW I2 SUPV ENAB:OffRange: FlexLogic operand POWER SWINGI2 SUPV: 0.200 puRange: 0.050 to 30.000 pu in steps of 0.001 POWER SWING FWDREACH: 50.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING QUAD FWDREACH MID: 60.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING QUAD FWDREACH OUT: 70.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING FWDRCA: 75°Range: 40 to 90° in steps of 1 POWER SWING REVREACH: 50.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING QUAD REVREACH MID: 60.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING QUAD REVREACH OUT: 70.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING REVRCA: 75°Range: 40 to 90° in steps of 1 POWER SWING OUTERLIMIT ANGLE: 120°Range: 40 to 140° in steps of 1 POWER SWING MIDDLELIMIT ANGLE: 90°Range: 40 to 140° in steps of 1