7-4 L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUALTARGETS MENU CHAPTER 7: COMMANDS AND TARGETS7There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDERCODE NOT UPDATED message displays.REBOOT RELAY — Restarts the relay so that changes to configuration settings can take effect. In most cases, if changes aremade to the configuration settings these changes do not take effect unless the relay is rebooted.SERVICE COMMAND — Performs specific L60 service actions. Presently, there are two service actions available. Code "20511"returns all settings to their factory default value. Code “101” is used to clear factory diagnostic information stored in thenon-volatile memory. If a code other than these two is entered, the command is ignored and no action is taken. Variousself-checking diagnostics are performed in the background while the L60 is running, and diagnostic information is storedon the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information iscleared before the L60 is shipped from the factory, the user can want to clear the diagnostic information for themselvesunder certain circumstances. For example, you clear diagnostic information after replacement of hardware. Once thediagnostic information is cleared, all self-checking variables are reset to their initial state and diagnostics restart fromscratch.SAVE VOLATILE DATA — Saves this data to compact flash memory prior to shutdown. This allows the saved data to be asrecent as possible instead of relying on the periodic timer to save the data.7.1.5 SecurityCOMMANDS SECURITYWith the CyberSentry option, this setting is available to enable or disable the following commands.ADMINISTRATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an administrator session.ENGINEER LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an engineer session.OPERATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session.CLEAR SECURITY DATA — Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all theoperands associated with the self-tests.7.2 Targets menuUPDATING...PLEASE WAITWith the CyberSentry option, the Administrator and Operator roles can initiate the Reboot Relay command. SECURITY ADMINISTRATORLOGOFF: NoRange: Yes, No ENGINEERLOGOFF: NoRange: Yes, No OPERATORLOGOFF: NoRange: Yes, No CLEAR SECURITY DATA:NoRange: Yes, NoTARGETS