Parker EME Introduction192-120114 N5 C3I22T11 June 2008 191.6.2. Conditions of utilization for UL certification Compax3SUL certifiction for Compax3Sconform to UL: according to UL508CCertified E-File_No.: E235 342The UL certification is documented by a ”UL” logo on the devi-ce (type specification plate).”UL” logoConditions of utilization The devices are only to be installed in a degree of contamination 2 environment(maximum). The devices must be appropriately protected (e.g. by a switching cabinet). The X2 terminals are not suitable for field wiring. Tightening torque of the field wiring terminals ( green Phoenix plugs) C3S0xxV2 0.57 - 0.79Nm 5 - 7Lb.in C3S1xxV2,C3S0xxV4, C3S150V40.57 - 0.79Nm 5 - 7Lb.in C3S300V4 1.25 - 1.7Nm 11 - 15Lb.in Temperature rating of field installed conductors shall be at least 60°C Use copperlines onlyPlease use the cables described in the accessories chapter (see page 340, seepage 342), they do have a temperature rating of at least 60°C. Maximum ambient temperature: 45°C. Suitable for use on a circuit capable of delivering not more than 5000 rms sym-metrical amperes and 480 volts maximum.ATTENTIONDanger of electric shock.Discharge time of the bus capacitator is 5 minutes. The drive provides internal motor overload protection.This must be set so that 200% of the motor nominal current are not exceeded. Cable cross-sections Mains input: corresponding to the recommended fuses. Motor cable: (see page 359) corresponding to the nominal output currents(see page 395, see page 394) Maximum cross-section limited by the terminals mm2 / AWG C3S0xxV2 2.5mm2 AWG 12 C3S1xxV2,C3S0xxV4, C3S150V44.0mm2 AWG 10 C3S300V4 6.0mm2 AWG 7