Table 2: Basic parameters G2.1Index Parameter Min Max Unit Default Cust ID DescriptionP2.15 Analogue input 2,reference offset 0 1 1 302 0 = 0-20 mA1 = 4 mA-20mAP2.16 Analogue outputfunction 0 8 1 3070 = Not used1 = Output freq. (0-fmax)2 = Freq. reference(0-fmax)3 = Motor speed(0-Motor nominalspeed)4 = Output current(0-InMotor)5 = Motor torque(0-TnMotor)6 = Motor power(0-PnMotor)7 = Motor voltage(0-UnMotor)8 = DC-link volt(0-1000V)P2.17 DIN3 function 0 7 1 3010 = Not used1 = Ext. fault, clos-ing cont.2 = Ext. fault,opening cont.3 = Run enable, cc4 = Run enable, oc5 = Force cp. to IO6 = Force cp. tokeypad7 = Force cp. tofieldbusP2.18 Preset speed 1 0.00 P2.2 Hz 0.00 105P2.19 Preset speed 2 0.00 P2.2 Hz 50.00 106P2.20 Automatic restart 0 1 0 731 0 = Disabled2 = Enabled1.4.3 KEYPAD CONTROL (CONTROL KEYPAD: MENU M3)The parameters for the selection of control place and direction on the keypad are listedbelow. See the Keypad control menu in the product's User Manual.BASIC APPLICATION VACON · 17LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/ 1