Fig. 95: Screenshot of NCDrive programming tool; Entering the address codeCAUTION!Be ABSOLUTELY sure not to connect two functions to one and same output in orderto avoid function overruns and to ensure flawless operation.NOTE!The inputs, unlike the outputs, cannot be changed in RUN state.9.9.3 DEFINING UNUSED INPUTS/OUTPUTSAll unused inputs and outputs must be given the board slot value 0 and the value 1 also forthe terminal number. The value 0.1 is also the default value for most of the functions.However, if you want to use the values of a digital input signal for e.g. testing purposes only,you can set the board slot value to 0 and the terminal number to any number between 2-10 toplace the input to a TRUE state. In other words, the value 1 corresponds to 'open contact' andvalues 2 to 10 to 'closed contact'.In case of analogue inputs, giving the value 1 for the terminal number corresponds to 0%signal level, value 2 corresponds to 20%, value 3 to 30% and so on. Giving value 10 for theterminal number corresponds to 100% signal level.VACON · 362 PARAMETER DESCRIPTIONS9 LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/