2.4.4 OUTPUT SIGNALS (CONTROL KEYPAD: MENU M2 -> G2.3Table 7: Output signals, G2.3Index Parameter Min Max Unit Default Cust ID DescriptionP2.3.1 Analogue output 1signal selection 0 A.1 464P2.3.2 Analogue outputfunction 0 8 1 3070 = Not used (20mA/10V)1 = Output freq. (0-fmax)2 = Freq. reference(0-fmax)3 = Motor speed(0-Motor nominalspeed)4 = Motor current(0-InMotor)5 = Motor torque(0-TnMotor)6 = Motor power(0-PnMotor)7 = Motor voltage(0-UnMotor)8 = DC-link volt(0-1000V)P2.3.3 Analogue outputfilter time 0.00 10.00 s 1.00 308 0 = No filteringP2.3.4 Analogue outputinversion 0 1 0 309 0 = Not inverted1 = InvertedP2.3.5 Analogue outputminimum 0 1 0 310 0 = 0 mA (0 V)1 = 4 mA (2 V)P2.3.6 Analogue outputscale 10 1000 % 100 311STANDARD APPLICATION VACON · 27LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/ 2