7.4.5 DRIVE CONTROL PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.4Table 97: Drive control parameters, G2.4Index Parameter Min Max Unit Default Cust ID DescriptionP2.4.1 Ramp 1 shape 0.0 10.0 s 0.1 5000 = Linear100 = full acc/decinc/dec tmesP2.4.2 Ramp 2 shape 0.0 10.0 s 0.0 5010 = Linear100 = full acc/decinc/dec tmesP2.4.3 Acceleration time2 0.1 3000.0 s 1.0 502P2.4.4 Deceleration time2 0.1 3000.0 s 1.0 503P2.4.5 Brake chopper 0 4 0 5040 = Disabled1 = Used whenrunning2 = External brakechopper3 = Used whenstopped/running4 = used when run-ning (no testing)P2.4.6 Start function 0 2 0 5050 = Ramp1 = Flying start2 = Conditional fly-ing startP2.4.7 Stop function 0 3 0 5060 = Coasting1 = Ramp2 = Ramp+Runenable coast3 = Coast+Runenable rampP2.4.8 DC braking cur-rent 0.00 IL A 0.7 x IH 507P2.4.9 DC braking timeat stop 0.00 600.00 s 0.00 508 0 = DC brake is offat stopP2.4.10Frequency to startDC braking duringramp stop0.10 10.00 Hz 1.50 515P2.4.11 DC braking timeat start 0.00 600.00 s 0.00 516 0 = DC brake is offat startP2.4.12 * Flux brake 0 1 0 520 0 = Off0 = OnVACON · 190 PUMP AND FAN CONTROL APPLICATION7 LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/