3.4.8 PROTECTIONS (CONTROL KEYPAD: MENU M2 -> G2.7Table 21: Protections, G2.7Index Parameter Min Max Unit Default Cust ID DescriptionP2.7.1 Response to 4 mAreference fault 0 5 0 7000 = No response1 = Warning2 = Warning+Previ-ous Freq.3 = Wrng+Preset-Freq 2.7.24 = Fault, stop acc.to 2.4.75 = Fault, stop bycoastingP2.7.2 4 mA referencefault frequency 0.00 P2.1.2 Hz 0.00 728P2.7.3 Response toexternal fault 0 3 2 701 0 = No response1 = Warning2 = Fault, stop acc.to 2.4.73 = Fault, stop bycoastingP2.7.4 Input phasesupervision 0 3 0 730P2.7.5 Response toundervoltage fault 0 1 0 7270 = Fault stored inhistoryFault not storedP2.7.6 Output phasesupervision 0 3 2 702 0 = No response1 = Warning2 = Fault, stop acc.to 2.4.73 = Fault, stop bycoastingP2.7.7 Earth fault protec-tion 0 3 2 703P2.7.8 Thermal protec-tion of the motor 0 3 2 704P2.7.9Motor ambienttemperature fac-tor-100.0 100.0 % 0.0 705P2.7.10 Motor cooling fac-tor at zero speed 0.0 150.0 % 40.0 706P2.7.11 Motor thermaltime constant 1 200 min Varies 707P2.7.12 Motor duty cycle 0 150 % 100 708P2.7.13 Stall protection 0 3 0 7090 = No response1 = Warning2 = Fault, stop acc.to 2.4.73 = Fault, stop bycoastingLOCAL/REMOTE CONTROL APPLICATION VACON · 59LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/ 3