3.4.9 AUTORESTART PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.8)Table 22: Autorestart parameters, G2.8Index Parameter Min Max Unit Default Cust ID DescriptionP2.8.1 Wait time 0.10 10.00 s 0.50 717P2.8.2 Trial time 0.00 60.00 s 30.00 718P2.8.3 Start function 0 2 0 7190 = Ramp1 = Flying start2 = According toP2.4.6P2.8.4Number of triesafter undervoltagetrip0 10 0 720P2.8.5Number of triesafter overvoltagetrip0 10 0 721P2.8.6Number of triesafter overcurrenttrip0 3 0 722P2.8.7Number of triesafter 4mA refer-ence trip0 10 0 723P2.8.8Number of triesafter motor tem-perature fault trip0 10 0 726P2.8.9Number of triesafter externalfault trip0 10 0 725P2.8.10Number of triesafter underloadfault trip0 10 0 7383.4.10 KEYPAD CONTROL (CONTROL KEYPAD: MENU M3)The parameters for the selection of control place and direction on the keypad are listedbelow. See the Keypad control menu in the product's User Manual.LOCAL/REMOTE CONTROL APPLICATION VACON · 61LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/ 3