I/O Modules 197WAGO I/O-SYSTEM 750I/O-IPC-C10E, CANopen Master18.2.2 Digital Output ModulesThe digital output modules use one bit per channel to represent the state of thechannel. These bits are mapped into the output process image.If analog output modules are in the node, the digital data is grouped in bytes andadded after the analog output data in the process image.1-Channel Digital Output Modules with Input Data750-523Input Process ImageBit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0Not usedStatus bitìManualoperationîOutput Process ImageBit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0Not usedControlsDO 1Channel12-Channel Digital Output Modules750-: 501, 502, 509, 512, 513, 514, 517 and 535 (and all variants)753-: 501, 502, 509, 512, 513, 514 and 517Output Process ImageBit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0ControlsDO 2Channel2ControlsDO 1Channel1