38 Installing and Removing the I/O-IPCWAGO-I/O-SYSTEM 750I/O-IPC-C10E, CANopen Master6.5 Connecting the I/O Module to the I/O-IPCAfter mounting the I/O-IPC on a mounting rail, connect the I/O modules requiredfor your application to the I/O-IPC. You can connect up to 64 750/753 Series I/OModules to the I/O-IPC. The number is dependent on the total length of theconnected I/O modules. This may amount to a maximum of 780mm, including theend module, and the maximum size of the process image for the input and outputdata cannot exceed 500 bytes in each case.Example of total length:If the individual I/O modules have a width of 12mm, 64 modules may beconnected, but if they are 24mm wide, then only 32 I/O modules may beconnected.With the optional WAGO internal data bus extension (consisting of the 750-628Coupler Module and 750-627 End Module), it is possible to use up to 250 I/Omodules. The same limitations apply in this case as for the use of 64 I/O-modules.InformationInformation on the use of the WAGO internal data bus extension can be found inthe 750-627 and 750-628 documentation, which can be obtained from the WAGOinternet site.InformationAdditional information and instructions for use for WAGO I/O modules can befound in the WAGO-I/O-SYSTEM 750/753 system description. The respectivemanuals and data sheets can be found at www.wago.com.Continued on the next page.