34 Description of I/O-IPC InterfacesWAGO-I/O-SYSTEM 750I/O-IPC-C10E, CANopen Master5.8 750-602 Power Supply ModuleThe field supply for the connected I/O modules, sensors and actuators is fed inthrough the power supply module.+ +Figure 9: Power supply modulePosition LED/Operating Element Color/StatusMeaning60 Earth - Connection of protective earth61 0 V DC - Ground (GND) of the supply voltage62 Field supply, 24 V DC - 24V supply voltage for the sensors/actuators.The power supply is protected against reversepolarity.For the supply of other field potentials; e.g.,230 VAC, appropriate power supply modulesare available. You can find detailedinformation on this in the manuals for thepower supply modules and in the 750-xxxsystem description.63 Power jumper contacts - Conduction of the field-side supply voltage tothe connected I/O modules.64 Data contacts - These make the supply voltage (5 V, 1 A)available for the electronics in the I/Omodules connected to the internal data bus.The supply voltage is provided by the I/O-IPC (connection X4).44 LED Green/off The LED lights up if the field supply isavailable (see Pos. 62). Otherwise, the LED isoff.636460 61 6263 6344