6 Implemented EtherNet/IP objects6.1 Standard CIP object classesSmartWire-DT Gateway EU5C-SWD-EIP-MODTCP 08/17 MN120003Z EN www.eaton.com 596.1.3 Assembly object 0x4The assembly object is used to group input or output data in order to be ableto easily read and write large volumes of data using a single connection. Theoutput data to all SmartWire-DT modules is grouped in instance 100. Theinputs of all SmartWire-DT modules are grouped in instance 101. The objectlength varies and depends on the number of SmartWire-DT modules andtheir data volumes. The maximum object length is 496 bytes for eachinstance.Overview of functionsClass AttributesCommon ServicesTable 10: Common ServicesClasses/InstancesAttribute/Services &ValueClassesAttributes 0x01, 0x02, 0x03, 0x04, 0x06, 0x07Services 0x0EInstancesAttributes 0x03, 0x04Services 0x10 (for instance 100 only), 0x0EFor explanations regarding the services, see Tabelle 6Attribute number Attribute Name Get/Set Data type Description &Value1 (0x01) REVISION G UINT Class version 0x00 022 (0x02) MAX CLASS ID G UINT Highest supported class number 0x00 653 (0x03) NUMBER OF INSTANCES G UINT Number of instances 0x00 024 (0x04) OPTIONAL ATTRIBUTE LISTNUMBER OF AttributsOPTIONAL AttributsG STRUCT ofUNITARRAY of UNITNumber of attributesList of optional attributes0x00 010x00 046 (0x06) MAX CLASS IDENTIFIER G UINT Highest number of the implementedclass attribute0x00 077 (0x07) MAX INSTANCE ATTRIBUTE G UINT Highest number of the implementedinstance attribute0x00 04Service code Class Instance100Instance101Service name14 (0x0E) yes yes yes Get_Attribute_SingleReturns the specific attribute's content16 (0x10) No yes No Set_Attribute_SingleModifies a single attribute.