8 What you need to know about SmartWire-DT8.1 Configurations84 SmartWire-DT Gateway EU5C-SWD-EIP-MODTCP 08/17 MN120003Z EN www.eaton.com8.1 ConfigurationsThe following different SWD configurations are possible:1 Planned SWD configurationBefore the SWD coordinator can start running, the device must knowwhich SWD modules are present and how their parameters have beenconfigured. This collected information is found in the planned SWD con-figuration.Depending on the field bus protocol that you will be using, you will becreating the planned SWD configuration in the PLC programming envi-ronment or in SWD assist.2 Target configurationPressing the "Config" configuration button on the device will make thesystem determine the actual configuration and store it as a target config-uration in the SWD coordinator.3 Actual configurationBy this is meant the actual physical configuration present on the SWDline. Every Every time SWD coordinator is started, the actual configura-tion is determined and compared with the stored target configura-tion.time SWD coordinator is started, the actual configuration is deter-mined and compared with the stored target configuration.8.2 Changing the planned SWD configuration in SWD assistTo change the configuration of the SWD line, e.g., to add a new module orreplace an existing one, you will have to change the planned SmartWire-DTconfiguration and import the target configuration again. Proceed as describedin → Section “3.1.1 Reading of target configuration”, page 30.Example: Changing or replacing a module on the SWD lineModule M22-SWD-K11LED-W has one changeover contact and one whiteLED. This module is to be replaced with an M22-SWD-K22LED-W module,which features two changeover contacts and one white LED. In order tochange the module, you would proceed as follows:▶ Switch the power supply off at the device.▶ Pull the M22-SWD-K11LED-W out of the external device plug.▶ Plug the M22-SWD-K22LED-W into the external device plug.▶ Switch on the power supply.The SWD LED will show a red light, indicating that, as expected, the mod-ules on the SWD line do not match the target configuration stored on thedevice.→ Please note that the planned SWD configuration and the projectconfiguration are not the same thing.While the planned SWD configuration describes the parametersand the layout of the modules on the SWD line, the project con-figuration is the description for the controller as such.