www.eaton.comNetworkManagement Card(Network-MS)User ManualNetwork Management Card – User Manual 34003991XT_EN/JC Page 11/143NMC also supplies alarms to the Intelligent Power Protector in order to trigger shutdowns or manage otherautomatic actions on protected servers.1.2.2 Direct sending of E-mailWhen a UPS event occurs, the Network Management Card can directly notify up to 4 addresses by e-mail. (seeE-mail Notification and E-mail message settings)1.2.3 Sending text messages (SMS)SMS notification requires the use of a third-party application that converts emails to SMS. The card offers thepossibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is compatible with mobiletelephone e-mail/SMS transfer systems proposed by ISPs. The format to be used depends on the serviceprovider.1.2.4 Compatibility with the Network Management Systems (NMS) – Trap sendingThe Network Management Cards are compatible with the major Network Management Systems (IBM Tivoli, CAUnicenter, HP Insight Manager). The Software Suite offering includes the necessary SNMP plug-ins to allow aneasy integration in the NMS. Events are notified by SNMP trap.• NMS can subscribe on page “Notified Applications”• The trap list is given in the appendix.1.2.5 Environment Sensor (option)The optional Environment Sensor (EMP) solution can be connected to the Card Settings port of theNetwork Management Cards.Environment Sensor enables measurement of temperature and humidity around the UPS, allows managingexternal alarms via 2 dry contacts and notification of alarms according to pre-programmed thresholds. (seeEnvironment Status and Environment Configuration)