www.eaton.comNetworkManagement Card(Network-MS)User ManualNetwork Management Card – User Manual 34003991XT_EN/JC Page 63/1434.4.6 Central shutdown configurationNote: Intelligent Power® Manager provides more advanced configuration management featuresClick on Notified Applications in the menu, then Configuration.This page is used to define either the "shutdown" or the "notification" settings used by the Intelligent PowerProtector that connects to Network Management Card. These settings are used by the Intelligent Power Protectorif they are in central-configuration mode or if their configuration is not valid.• Shutdown duration: the shutdown duration necessary to properly shutdown the computer.• Shutdown after: the time available to the user from the power failure until the launch of the shutoffsequence of the UPS and equipment. This parameter is optional. Uncheck the box if you wish not to usethis parameter.• Broadcast : Sends network notifications to the Administrators and Users groups on events declared inthe server hosting the NSMIf you wish to set up a new configuration for the Network Shutdown Modules already set to "central-configurationmode", proceed as follows:• Change the IPP parameters in the "Notified Applications" page.• Click the "Save" button.• In this page, select the IPPs for which you want to apply the new configuration.• Press the "Remove" button.• The IPPs selected will disconnect then reconnect and use the new configuration.