6 Parameters6.5 Parameter description102 DE1 variable speed starter 09/14 MN040011EN www.eaton.comIn both settings (P-12 = 1, P-12 = 2), the control terminals can be configuredwith P-15 as follows:Table 27: Configuration with external keypad6.5.6.2 Control terminals and Modbus RTUP-12 = 3 (Modbus RTU)P-15(Mode)DI1 DI2 DI3 AI1/DI40 FWD REV FF1 n. F.1 FWD REV EXTFLT n. F.2 FWD REV FF20 FF2 13 FWD FF1 EXTFLT n. F.4 FWD UP FF1 DOWN5 FWD UP EXTFLT DOWN6 FWD REV UP DOWN7 FWD FF2 0 EXTFLT FF2 18 ENA DIR FF1 n. F.9 ENA DIR EXTFLT n. F.n.F. = No function.When configured this way, the control terminals “n.F.” will have no functionwhatsoever!→ → Section 7.3, “Control terminal functions with Modbus RTU”,page 116 describes the configuration options (P-15) for thecontrol terminals when the device is used together withModbus RTU.