3 Installation3.3 Electrical InstallationDE1 variable speed starter 09/14 MN040011EN www.eaton.com 533.3.8.4 Connection examples control sectionTable 9: Connection examples with the mode 0 default setting (P-15)connection terminals DescriptionSoft start functionMotor start carried out with configured time parameters and preselected operating direction.DI1 = Clockwise rotation field enable (FWD)A1/DI4 = Frequency reference (f-REF ), +10 V = Maximum 50/60 Hz frequency (P-09)Acceleration ramp time: 5 seconds (P-03)If DI1 is switched off, the motor will be stopped in a controlled manner with a decelerationtime of 5 seconds (P-04)Variable speed starter (standard, default setting)Motor start in both operating directions with variable speedDI1 = Clockwise rotation field enable (FWD)DI2 = Anticlockwise rotation field enable (REV)DI3 = Fixed frequency (FF1 = 20 Hz); overwrites analog variable frequency reference valuef-REF (0 - 10 V)A1/DI4 = Frequency reference (f-REF ), 0 - 10 V = 0 to 50/60 Hz max. frequency (P-09)Acceleration ramp time: 5 seconds (P-03)Deceleration ramp time: 5 seconds (P-04)R1: Reference value potentiometer (e.g., fixed value of 4.7 kΩ)f50(60)[Hz]FWD5f-REF5 t [s]AI1DI4DI3DI2DI14321+10 VX1+10 V< 20 mA0 V+10...+24 V DCFWDf-REFAI1DI4DI3DI2DI14321+10 VX1R1+10 V< 20 mA0 V+10...+24 V DCFF1REVFWDf-REFf50(60)[Hz]20FWD5f-REFFF1REVf-REF5t [s]