10 Fault messages10.2 Fault logDE1 variable speed starter 09/14 MN040011EN www.eaton.com 165The following example shows how to access the fault memory with theDX-KEY-LED keypad:View DescriptionOperating state StopPress the OK button and hold it down for two seconds.The most recently accessed parameter will be shown (e.g., P-00)The last digit on the display will flash.Use the ▲ (UP) and ▼ (DOWN) arrow keys to select the fault memoryparameter (P-13) and confirm by pressing the OK button.Last fault message;Example: P-dEf (default parameters):The device was restored to its default settings.Press the ▲ (UP) arrow key to go to the next fault message.Second most recent fault message:Example: U-Volt (undervoltage signal).The decimal point on the right will flash (= second most recent faultmessage).If you press the ▲ (UP) arrow key, the third most recent fault messagewill be shown.Third most recent fault message:Example: E-trip (external fault message).The two decimal points on the right will flash (= third most recent faultmessage).If you press the ▲ (UP) arrow key again, the fourth most recent faultmessage will be shown.Fourth most recent fault message;Example: U-Volt (undervoltage signal)The three decimal points on the right will flash (= fourth most recent faultmessage).