3 Installation3.3 Electrical InstallationDE1 variable speed starter 09/14 MN040011EN www.eaton.com 573.3.8.7 Relay contact (RUN)Control terminals 13 and 14 are connected to the DE1 variable speedstarter's internal potential-free relay contact (N/O).• This contact will close when there is an enable signal (FWD, REV, ENA)and there are no fault messages present.• The contact will open immediately when there is a fault messagepresent.• The contact will open if the enable signal is switched off (FWD, REV,ENA) and the motor coasts uncontrolled (P-05 default setting = 0).• The contact will open after a delay, once the deceleration time set inP-04 elapses (f 2 = 0 Hz), if the enable signal (FWD, REV, ENA) isswitched off.• The contact will open after a delay if the enable signal (FWD, REV, ENA)is switched off and the motor is brought to a speed of 0 in line with thedeceleration ramp (P-04 ramp time).The supply data for control terminals 13 and 14 are:• 250 V AC, max. 6 A AC1• 30 V DC, max. 5 A DC1In order to ensure smooth operation, we recommend adding suppressorcircuits to inductive loads (e.g., coupling relays, contactors) as follows:figure 44: Connection examples with suppressor circuitDrive relay output250 V ∼ ≦ 6 A, AC-130 V ⎓ ≦ 5 A, DC-113 14RunK1IK1 1314ACDCACVaristor (+)(- )DCDiodeACRC filter