7 Modbus RTU7.4 Operating mode Modbus RTUDE1 variable speed starter 09/14 MN040011EN www.eaton.com 125Type (ID 12)Power rating (ID 13)The specified value will always have two decimal places.Example:Register 13 = 150 → The device has an output of 1.50 – based on ID 12(kW or HP, single-phase or 3-phase, 230 V or 400 V).Voltage (ID 14)Specifies the device's specified input voltage.Example: 230 ≙ 230 VControl section software version (ID 15)Specifies the software version of the control section with two decimalplaces.Power section software version (ID 16)Specifies the software version of the power section with two decimal places.Speed start detection (ID 17)Device identification 8x x x x (hex) DescriptionPower index (country-specific)kW (for 50 Hz)HP (for 60 Hz)Phase index (mains connection)0 = single-phase (in DE1-12… devices)1 = 3-phase (in DE1-34… devices)Voltage class2 = 230 V (at DE1-12…)3 = 400 V (at DE1-34…)Frame size (FS)1 = FS12 = FS2