6 Parameters6.5 Parameter description92 DE1 variable speed starter 09/14 MN040011EN www.eaton.comOnce the motor winding cools down (= the thermistors cool down), the faultmessage can be reset, provided the resistance has fallen below 1,600 Ω.figure 65: Connection example with thermistor and trip characteristicTable 22: Parameter P-15, P-193EXTFLT+10 VϑϑϑM3 ~607501650400012000ϑ [°C]3600 Ω → EXTFLT1600 Ω → ResetTolerance limitTNF-20 grdTNFTNF-5 grdTNF+5 grdTNF+15 grdR[Ω]PNU Modbus ID Access right Name Value DS DescriptionRUN,STOPro/rwP-15 143 STOP rw DI ConfigSelect0 - 9 0 Function of the control terminalsWhen P-12 = 0, control terminals DI1 to DI4can be configured with the followingfunctions:Note:The assigned control terminal functionswill depend on the value set in P-12.P-19 147 STOP rw DI3 Logic 0/1 0 Digital input DI3, LogicDI3 logic when assigned the EXTFLT(external fault) function in P-15 (= 1, 3, 5, 7,or 9):0: High = OK, Low = EXTFLT1: Low = OK, High = EXTFLTLED fault message (Fault Code):„2 pulses - external fault“Mode DI1 DI2 DI3 AI1/DI40 FWD REV FF1 REF1 FWD REV EXTFLT REF2 FWD REV FF2 0 FF213 FWD FF1 EXTFLT REV4 FWD UP FF1 DOWN5 FWD UP EXTFLT DOWN6 FWD REV UP DOWN7 FWD FF20 EXTFLT FF218 START DIR FF1 REF9 START DIR EXTFLT REF