6 ParametersDE1 variable speed starter 09/14 MN040011EN www.eaton.com 776 ParametersFollowing is a description of the DE1 variable speed starter's parameters andfunctions. These parameters can be accessed using the device's front RJ45interface and require optionally available interface devices in order to bedisplayed and adjusted:• DX-KEY-LED keypad (version 1.2 or higher) with the corresponding3 m-long patch cable with RJ45 connectors• DX-CBL-PC-1M5 interface converter (RJ45 to USB, galvanically isolated,with 1.5 m-long cable) for connecting to a computer with thedrivesConnect parameter configuration program.• DX-COM-STICK communication stick for copying and saving parameterson other DE1 devices, as well as for establishing a wireless connection(Bluetooth) to a computer with the drivesConnect parameterconfiguration program.figure 56: RJ 45 interfaceTable 15: Pin assignment of the RJ45 interface→ The interface devices listed here are not provided as standardwith the DE1 variable speed starter.Pin Description1 Not used (no function)2 Not used (no function)3 0 V4 OP bus (Operation Bus) / External keypad / -PC connection5 OP bus (operation bus) / External keypad / +PC connection6 +24 V, DC power supply7 RS485- / Modbus RTU (A)8 RS485+ / Modbus RTU (B)RJ45L1/L L2/N L3U V W0 V +10 V 1 2 3 4 13 141 2 3 4 5 6 7 8