6 Parameters6.5 Parameter description94 DE1 variable speed starter 09/14 MN040011EN www.eaton.comP-081) 136 STOP rw Motor NomCurrent(10 - 100 %) x I e I e Rated operational current of the motorBy default, the value in P-08 will beidentical to the DE1 variable speed starter'srated operational current(Ie).The rated motor current can be changedhere in order to adjust the motor protectionfunction (I2t).Note:If an overload lasts for an extended periodof time, the DE1 variable speed starter willbe automatically switched off with thefollowing LED fault message (Fault Code):"1 pulse – overload."P-09 137 STOP rw Motor NomFrequency20.0 - 300 Hz 50 Hz(60 Hz)Motor’s rated frequencyThe motor frequency at the rated operatingvoltage (P-07).P-10 138 STOP rw Motor NomSpeed0/200 - 15000 rpm(18000 rpm)0 Rated motor speedDisplay value:0: Output frequency in Hz≧ 200: rpm. All frequency-based parametervalues will be converted and shown in rpm.At the same time, slip compensation willbe activated.Note:Slip compensation will not be activated if asynchronous speed value is entered (e.g.,3,000 rpm for 50 Hz – this is thesynchronous speed of a 2-pole motor).P-11 139 RUN rw V-Boost 0.0 - 40.0 % 0.0 % Voltage BoostOutput voltage boost at low outputfrequencies. The value set here will be thestart voltage and will be calculated as apercentage of the motor's rated operatingvoltage (P-07). V-Boost is effective up toapprox. 50% of the motor's rated frequency(P-09).Note:The voltage increase will result in a higherstarting torque and will improve torquebehaviour at low speeds. In addition, themotor current will be increased, resulting inincreased motor heating.1) The parameter's values will not be copied if the parameters are copied to a DE1 variable speed starter with a different output rating.PNU Modbus ID Access right Name Value DS DescriptionRUN,STOPro/rw