12-3Data subject to change without notice 7/07. © 2007 GE DrivesMonitoring parameter registersAddress Code Description Unit Range Min. unit Read Data/ Write Format2049 M01 Frequency command (finalcommand)- - 20000–20000 (max. frequencyat ± 20000)1 R 22053 M05 Frequency command (finalcommand)Hz 0–400.00 0.01 R 52054 M06 Actual frequency - - 20000–20000 1 R 2(max. frequency at ± 20000)2055 M07 Actual torque value % - 200.00–200.00 0.01 R 62056 M08 Torque current % - 200.00–200.00 0.01 R 62057 M09 Output frequency Hz 0.00–400.00 0.01 R 52058 M10 Motor output (inputelectric power)% 0.00–200.00 0.01 R 52059 M11 Output current r. m. s. % 0.00–200.00 (inverter rating at100.00)0.01 R 52060 M12 Output voltage r. m. s. V 0.0–600.0 1 R 32061 M13 Operation command (finalcommand)- Refer to data format [14] - R 142062 M14 Operating state - Refer to data format [16] - R 162063 M15 Universal output terminaldata- Refer to data format [15] - R 152064 M16 Fault memory 0 - Refer to data format [10] - R 102065 M17 Fault memory 1 - 102066 M18 Fault memory 2 - 102067 M19 Fault memory 3 - 102068 M20 Integrated operating time h 0–65535 1 R 12069 M21 DC link voltage V 0–1000 1 R 12071 M23 Type code - Refer to data format [17] - R 172072 M24 Drive capacity code - Refer to data format [11] - R 112073 M25 ROM version - 0–64999 1 R 12074 M26 Transmission errorprocessing code- Refer to data format [20] - R 202075 M27 Frequency command atalarm (final command)- - 20000–20000 (max. frequencyat ±20000 )1 R 22079 M31 Frequency command atalarm (final command)Hz 0–400.00 0.01 R 52080 M32 Actual frequency at alarm - - 20000–20000 1 R 2(max. frequency a t ± 20000)2081 M33 Actual torque at alarm % - 200.00 – 200.00 0.01 R 62082 M34 Torque current at alarm % - 200.00 – 200.00 0.01 R 62083 M35 Output frequency at alarm Hz 0.00 – 400. 0.01 R 52084 M36 Motor output at alarm(input power)% 0.00–200.00 0.01 R 52085 M37 Output current r.m.s. atalarm% 0.00 – 200.00 (inverter rating at100.00)0.01 R 52086 M38 Output voltage effectivevalue at alarmV 0.0 – 600.0 1 R 32087 M39 Operation command atalarm- Refer to data format [14] - R 142088 M40 Operating state at alarm - Refer to data format [16] - R 162089 M41 Universal output terminaldata at alarm- Refer to data format [15] - R 152090 M42 Integrated operation timeat alarmh 0–65535 1 R 12091 M43 DC link voltage at alarm V 0–1000 1 R 12092 M44 Inverter internal air temp.at alarm°C 0–120 1 R 12093 M45 Cooling fin temp. at alarm °C 0–120 1 R 12094 M46 Life of main circuitcapacitor.% 0.0–100.0 0.1 R 32095 M47 Life of printed circuitboard capacitor.h 0–65535 1 R 12096 M48 Life of cooling fan. h 0–65535 1 R 1