1-4 Data subject to change without notice 7/07. © 2007 GE Drives1.6 AF-300 P11 Drive Ratings Efficiency and Watts LossHP RatingRated OutputCurrent (A)Rated OutputPower (KVA)Efficiency at 2KHz(%)Efficiency at15KHz (%)Watts Loss at2KHz (W)Watts Loss at15KHz (W) Internal DB (W)230VAC0.25 1.5 0.59 92.0 90.5 25 30 N/A0.5 3 1.1 93.5 91.7 35 45 N/A1 5 1.9 94.9 94.0 50 60 N/A2 8 3.1 95.7 94.1 80 110 N/A3 11 4.3 95.9 94.9 110 140 N/A5 17 6.7 96.2 95.4 170 210 N/A7.5 22 8.7 96.2 95.2 210 280 N/A10 29 11 96.5 95.3 290 370 N/A15 42 16 96.4 95.2 410 550 N/A20 55 21 96.9 95.9 500 670 N/A25 67 26 96.8 95.8 630 840 N/A30 78 31 96.5 95.5 770 1030 N/A2KHz (%) 10KHz (%) 2KHz (W) 10KHz (W)40 115 45 97.2 96.8 950 1100 N/A50 145 57 97.0 96.7 1250 1400 N/A60 180 71 97.1 96.6 1500 1750 N/A75 215 85 97.3 96.6 1700 1950 N/A100 283 112 97.4 97.0 2200 2500 N/A2KHz (%) 6KHz (%) 2KHz (W) 6KHz (W)125 346 137 97.4 97.2 2650 2800 N/A150 415 165 97.4 97.3 3200 3350 N/A460VAC0.5 1.5 1.1 93.5 89.3 35 60 N/A1 2.5 1.9 95.4 91.7 45 85 N/A2 3.7 2.9 96.7 94.1 60 110 N/A3 5.5 4.3 97.0 94.5 80 150 N/A5 9 7.1 97.1 95.0 130 230 N/A7.5 12.5 9.9 97.3 95.3 160 290 N/A10 16.5 13.1 97.3 95.4 210 370 N/A15 23 18.3 97.6 95.9 300 520 N/A20 30 23.9 97.9 96.5 360 610 N/A25 37 29.4 97.8 96.4 460 770 N/A30 44 35 97.8 96.4 530 870 N/A2KHz (%) 10KHz (%) 2KHz (W) 10KHz (W)40 60 47 97.8 96.9 750 1050 N/A50 75 59 97.7 96.9 950 1300 N/A60 91 72 97.8 97.0 1100 1550 N/A75 112 89 97.8 97.0 1350 1900 N/A100 150 119 97.8 97.1 1800 2450 N/A2KHz (%) 6KHz (%) 2KHz (W) 6KHz (W)125 176 140 98.1 97.8 1850 2200 N/A150 210 167 98.0 97.8 2400 2750 N/A200 253 202 98.0 97.7 2900 3350 N/A250 304 242 98.1 97.8 3250 3800 N/A300 377 300 98.1 97.8 4250 4900 N/A350 415 330 98.2 97.9 4350 5100 N/A400 485 386 98.1 97.8 5100 5900 N/A450 520 414 98.1 97.8 5700 6650 N/A500 650 518 98.2 97.9 6900 8050 N/A600 740 590 98.1 97.8 8050 9350 N/A700 840 669 98.2 97.9 8900 10400 N/A800 960 765 98.1 97.8 10300 12100 N/A