5-3Func. Factory Setting Data ChangeNo. Setting Range Unit Min. 30 HP 40 HP Format during opC20 JOG frequency C20 JOG Hz 0.00 to 120.00 Hz Hz 0.01 5.00 5 YC21 PATTERN (mode select) C21 PATTERN 0,1,2 - - 0 1operationC22 (Stage 1) C22 STAGE 1 Operation time: 0.00 to 6000 s s 0.01 0.00 F1 13C23 (Stage 2) C23 STAGE 2 F1 to F4 and R1 to R4 0.00 F1 13C24 (Stage 3) C24 STAGE 3 0.00 F1 13C25 (Stage 4) C25 STAGE 4 0.00 F1 13C26 (Stage 5) C26 STAGE 5 0.00 F1 13C27 (Stage 6) C27 STAGE 6 0.00 F1 13C28 (Stage 7) C28 STAGE 7 0.00 F1 13C30 Frequency command 2 C30 FREQ CMD 2 0 to 11 - - 2 1 NC31 Offset adjust (terminal [12]) C31 BIAS 12 -100.0 to +100.0% % 0.1 0.0 4 YC32 (terminal [C1]) C32 GAIN 12 0.0 to +200.0% % 0.1 100.0 3 Y5-31 C33 Analog setting signal filter C33 REF FILTER 0.00 to 5.00s s 0.01 0.05 5 YP:Motor ParametersP01 Number of motor 1 poles P01 M1 POLES 2 to 14 - 2 4 9 NP02 Motor 1 (capacity) P02 M1-CAP Up to 30 HP: 0.01 to 60 HP Hp 0.01 motor capacity 540 HP and above: 0.01 to 800 HPP03 (rated current) P03 M1-Ir 0.00 to 2000 A A 0.01 motor rated current 19 NP04 (tuning) P04 M1 TUN1 0, 1, 2 - - 0 21 NP05 (on-line tuning) P05 M1 TUN2 0, 1 - - 0 1 NP06 (no-load current) P06 M1-Io 0.00 to 2000 A A 0.01 standard rated value 19 NP07 (%R1 setting) P07 M1-%R1 0.00 to 50.00% % 0.01 standard rated value 5 YP08 (%X setting) P08 M1-%X 0.00 to 50.00% % 0.01 standard rated value 5 YP09 Slip compensation control P09 SLIP COMP1 0.00 to 15.00 Hz Hz 0.01 0.00 5 YH:High Performance FunctionsH03 Data initializing H03 DATA INIT 0, 1 - - 0 1 NH04 Auto-reset (times) H04 AUTO-RESET 0, 1 to 10 times - 1 0 1 YH05 (reset interval) H05 RESET INT 2 to 20 s s 1 5 1 YH06 Fan stop operation H06 FAN STOP 0, 1 - - 0 1 YH07 ACC/DEC pattern (mode select) H07 ACC PTN 0,1,2,3 - - 0 1 NH08 Rev. phase sequence lock H08 REV LOCK 0, 1 - - 0 1 NH09 Start mode H09 START MODE 0, 1, 2 - -- 0 1 NH10 Energy-saving operation H10 ENERGY SAV 0, 1 - - 1 1 YH11 DEC mode H11 DEC MODE 0, 1 - - 0 1 YH12 Instantaneous OC limiting H12 INST CL 0, 1 - - 1 1 NH13 Auto-restart (restart time) H13 RESTART t 0.1 to 10.0 s s 0.1 0.1 0.5 3 NH14 (freq. fall rate) H14 FALL RATE 0.00 to 100.00 Hz/s Hz/s 0.01 10.00 5H15 (holding DC voltage) H15 HOLD V 3-phase, 230V class: 200 to 300V V 1 200V class: 235V 13-phase, 460V class: 400 to 600V 400V class: 470VH16 (OPR command self hold time) H16 SELFHOLD t 0.0 to 30.0 s, 999 s 0.1 999 3 NH19 Active drive H19 AUT RED 0, 1 - - 0 1 YH20 PID control (mode select) H20 PID MODE 0, 1, 2 -- - 0 1 N5-38 H21 (feedback signal) H21 FB SIGNAL 0, 1, 2, 3 - - 1 1 NH22 (P-gain) H22 P-GAIN 0.01 to 10.00 times - 0.01 0.1 5 YH23 (I-gain) H23 I-GAIN 0.0, 0.1 to 3600 s s 0.1 0.0 3 YH24 (D-gain) H24 D-GAIN 0.00 s , 0.01 to 10.0 s s 0.01 0.00 5 YH25 (feedback filter) H25 FB FILTER 0.0 to 60.0 s s 0.1 0.5 3 YH26 PTC thermistor (mode select) H26 PTC MODE 0, 1 0 1 YH27 (level) H27 PTC LEVEL 0.00 to 5.00V V 0.01 1.60 5 YH30 Serial link (function select) H30 LINK FUNC 0, 1, 2, 3 - - 0 1 YH31 Modbus-RTU (address) H31 ADDRESS 0 (broadcast), 1 to 247 - 1 1 1 NH32 (mode select on no response error) H32 MODE ON ER 0, 1, 2, 3 - - 0 1 YH33 (timer) H33 TIMER 0.0 to 60.0 s s - 2.0 3 YH34 (baud rate) H34 BAUD RATE 0, 1, 2, 3 - - 1 1 YH35 (data length) H35 LENGTH 0 (8-bit fixed) - - 0 1 YH36 (parity check) H36 PARITY 0, 1, 2 - - 0 1 YH37 (stop bits) H37 STOP BITS 0 (2-bit), 1(1-bit) - - 0 1 YH38 (no response error detection time) H38 NO RES t 0 (no detection), 1 to 60 s s 1 0 1 YH39 (response interval) H39 INTERVAL 0.00 to 1.00 s s 0.01 0.01 5 Y5-425-435-39/40Pg.5-295-29/305-305-375-41Name LCD DisplayNNYY5-365-325-335-345-35