2-17Data subject to change without notice 7/07. © 2007 GE Drives2.3.6 DC Link ReactorDimensions in inchesTerminalWidth DepthHeightNote:• AF-300 P11 Drives rated 100 Hp and above are furnished with a DC link reactor. This reactor must be installedbetween terminal P1 and P+ prior to commissioning of the Drive.• The weight of the DC Link Reactor is not included with that of the Drive.• DC Link Reactor is provided as open type and is separately mounted. Enclosure to be provided by others.Hp Model No. Width Depth Height Weight Loss [W]230V P11100 DCR2-75B 7.87 10.63 7.09 37 55125 DCR2-90B 7.09 11.02 8.46 37 57150 DCR2-110B 7.48 12.99 9.05 46 67460V P11100 DCR4-75B 7.48 10.63 6.89 35 58125 DCR4-90B 7.48 11.02 7.87 44 64150 DCR4-110B 7.48 11.02 7.87 46 73200 DCR4-132B 7.87 11.02 8.07 55 84250 DCR4-160B 8.27 12.6 8.07 68 90300 DCR4-200B 8.27 12.99 9.06 75 126350 DCR4-220B 8.66 13.78 9.06 81 131400 DCR4-280B 8.66 14.57 9.65 95 133450 DCR4-280B 8.66 14.57 9.65 95 150500 DCR4-355B 9.84 12.99 8.78 99 205600 DCR4-400B 9.84 13.78 9.17 106 215700 DCR4-450B 10.63 13.78 10.35 121 272800 DCR4-500B 11.1 14.17 10.35 143 292