Critical PowerModifications reserved Page 103/146GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx User Manual TLE Series 600 & 800 CE S18.1 PROCEDURES FOR SINGLE TLE SERIES 600 & 8008.1.1 Initial start-up of the TLE Series 600 & 800WARNING !Before proceeding to turn on the UPS system, ensure that the AC and DC externalisolators are OFF, and prevent their inadvertent operation.Ensure that the Output Load distribution can be powered and all the OutputIsolators are open.This procedure must be performed for the first start-up following the installation, with the UPScompletely switched Off and not powered.Open the front door and make sure that: All the connections to the input/output terminals or bus bars of the UPS have been made correctly. The safety screens are fixed in their position. The switch “Q1 –UPS Output” is open (Pos. O) and the “External Battery Protections” must be open(Pos. O).Q1 UPS Output switchLEDs on Synoptic DiagramLED 1 RectifierLED 2 InverterLED 3 Booster/ Battery chargerLED 4 Automatic BypassLED 5 LOAD on UPSLED ALARM LED LOAD PROTECTEDCommand Inverter ON Command Inverter OFFCommandSystem shutdownCommandSystem shutdown RESET1. Switch-ON the Mains voltage from the input distribution (both Rectifier and Bypass ifseparated).The UPS performs a “Self-test”.A successful termination of the tests will be indicated with Overall testresults “OK”.Commissioning cannot be continued should one or more tests resultto be negative. Please contact in this case your Service Centre.At this stage the Electronic Power Supply and Control Panel are switchedON and the Buzzer sounds.Press “MUTE” key to reset Acoustical Alarm.LED ALARM remains lit.Continue ►TLES_UL_1000_S1_Switch Q1_01Q10 OFFI ON