Critical PowerModifications reserved Page 92/146GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx User Manual TLE Series 600 & 800 CE S1eBOOST SCREEN (option)This screen is displayed only wheneBoost™ Operation Mode is available(option).EnabledThis parameter (values Yes/No) enablesor disables the eBoost™ OperationMode.If the value is “Yes” and the current timeis in the interval for the current day, theeBoost™ Operation Mode is active.In case of RPA Parallel SystemIf eBoost™ Operation Mode is currently disabled (No) and Q1 is closed, whenprogramming it to enable (Yes) the selected configuration will automatically bepropagated to all units in the RPA Parallel System.The activation / deactivation of eBoost™ Operation Mode is indicated each time in the event list.In order to check the inverter function, at least 1 minute of VFI mode must be programmed during theweek (the Yes/No parameter is automatically disabled if this condition is not satisfied).In case this minimum time in VFI mode is not respected, the eBoost™ Operation Mode will be disabled.If the value is “No”, the UPS is normally operating in VFI / double conversion mode at all times.When the UPS is in eBoost™ Operating Mode the eBoost LED is ON (greenlight).NOTE !The configuration of the activation schedule can only be updated when eBoost™ OperationMode is disabled (Enabled: No).DAYFor the weekdays from “Monday to Sunday”, the edit mode (edit day) allows to define time intervalswhen the UPS is operating in eBoost™ Operation Mode. The hour is given in 24-hour format.These intervals are defined by:Start Time: The hour of the day after which the eBoost™ Operation Mode is enabled.The eBoost™ Operation Mode is enabled until the following “Stop Time” time is reached(the “Stop Time” time of the same day if this is later than the “Start Time” time, the “StopTime” time of the following day otherwise).Stop Time: The hour of the day before which the eBoost™ Operation Mode is enabled.The eBoost™ Operation Mode is enabled starting from the preceding “Start Time” time (the “Start Time”time of the same day if this is earlier than the “Stop Time” time, the “Start Time” time of the previousday otherwise).Identical times for “Start Time” and “Stop Time” maintain the existing mode only in case the previouscommand was “Start Time” and the following command will be “Stop Time”.